IT has high electrical and mechanical characteristics with some grades
having a high heat resistance of temperature class F.
 |
Epoxy Resin Glass Fabric
|
- Type Hgw 2375 DIN 7735
- EN EP GC 21
Description
The main advantages of this grade are the high electrical and mechanical
characteristics. Exceptional interlayer bonding allows for ease of
machining. These tubes comply with temperature class B (130°C).
They can also be supplied in flame retardent performance complying with
V-0 according to UL Subject 94.
|
 |
Epoxy Resin Glass Fabric
|
- Type Hgw 2375.4 DIN 7735
- EN EP GC 22
Description
This grade has a high heat resistance up to 155°C (temperature class F)
and is mainly used as insulation tubing in transformers.
|

The following properties are based according to DIN 7735 and DIN EN 61212-3-1 .
 |
|
Grade |
Unit |
Values |
 |
DIN 53 452 |
N/mm² |
300 |
 |
DIN 53 455 |
N/mm² |
200 |
 |
DIN 53 454 |
N/mm² |
150 |
| Modulus of Elasticity (informational) |
DIN 53 457 |
N/mm² |
18 x 10³ |
| |
 |
|
Grade |
Unit |
Values |
 |
DIN 53 452 |
N/mm² |
300 |
 |
DIN 53 455 |
N/mm² |
200 |
 |
DIN 53 454 |
N/mm² |
150 |
| Modulus of Elasticity (informational) |
DIN 53 457 |
N/mm² |
18 x 10³ |
| |
DIN EN 61212 has been accepted between 1994 and 1996 and
replaces DIN 7735.

The following properties are based according to DIN 7735 and DIN EN 61212-3-1 .
 |
|
Grade |
Unit |
Values |
| Resistance Between Plugs |
DIN 53 482 |
Ohm |
 |
| 1 Minute Test Voltage Parallel, 25 mm dist. |
DIN 53 481 |
kV |
40 |
| 1 Minute Test Voltage Perpendicular, 3 mm dist. |
DIN 53 481 |
kV |
30 |
 |
DIN 53 483 |
- |
0,05 |
| Tracking Resistanct CTI |
IEC 112 |
- |
18 |
| |
 |
|
Grade |
Unit |
Values |
| Resistance Between Plugs |
DIN 53 482 |
Ohm |
 |
| 1 Minute Test Voltage Parallel, 25 mm dist. |
DIN 53 481 |
kV |
40 |
| 1 Minute Test Voltage Perpendicular, 3 mm dist. |
DIN 53 481 |
kV |
30 |
 |
DIN 53 483 |
- |
0,05 |
| Tracking Resistanct CTI |
IEC 112 |
- |
18 |
| |
DIN EN 61212 has been accepted between 1994 and 1996 and
replaces DIN 7735.

The following properties are based according to DIN 7735 and DIN EN 61212-3-1 .
 |
|
Grade |
Unit |
Values |
| Bulk Density |
DIN 53 479 |
g/mm³ |
1.7 - 1.9 |
| Temperature Index |
VDE 0304/2 |
°C |
130 |
| Water Absorption |
DIN 53 495 |
- |
low |
|   |
 |
|
Grade |
Unit |
Values |
| Bulk Density |
DIN 53 479 |
g/mm³ |
1.7 - 1.9 |
| Temperature Index |
VDE 0304/2 |
°C |
155 |
| Water Absorption |
DIN 53 495 |
- |
low |
|   |
DIN EN 61212 has been accepted between 1994 and 1996 and
replaces DIN 7735.

Permissible deviations according to DIN 40 607.
Nominal Dimension (mm) |
Inner Diameter |
|
Nominal Dimension (mm) |
Outer Diameter |
| 20 - 30 |
0.15 |
|
23 - 34 |
0.20 |
| 31 - 50 |
0.20 |
|
35 - 80 |
0.30 |
| 51 - 70 |
0.25 |
|
81 - 153 |
0.50 |
| 71 - 100 |
0.30 |
|
The permissible deviation of the wall thickness for inner diameters
of 150mm and more is 10% of the nominal value
of the wall thickness.
|
| 101 - 140 |
0.50 |
|
| 141 - 200 |
0.70 |
|
| 201 - 500 |
1.00 |
|
| 500 and more |
1.50 |
|
All data and values of this technical information have been ascertained with care.
Taking into consideration the multiplicity of both usage conditions and the process
and application technologies, the data and information supplied represent lead values
of a non-binding nature so that no warranty claims can be derived therefrom. Above all,
in addition to our general sales conditions, only agreements made in writing are
regarded as being binding.

|
|